[PIE] LOOP CALIBRATOR PIECAL 532
mA/Voltage Loop Calibrator with Loop Diagnostics
제품특징
True ±0.012% of reading accuracy
Source and Read 0.000-24.000 mA
Simulate 2-Wire Transmitters Power 2-Wire Transmitters and Read 0.000-24.000mA
Display current in mA or -25.00-125.00 % of 4-20 mA
Read 0.00 to ± 30.00 VDC with 4X over range ability
Source 0.000 to 24.000 VDC with up to 20mA output
Direct Calibration 1.000V to 5.000V
Auto Step or Ramp
Selectable step sizes, time in-between steps & soak time
Full 5 Digit Display
Uses (1) 9 Volt alkaline battery
Superior battery life of 40 hours under typical continuous usage
Easy access to battery compartment
240 VAC Tolerant
Current Leak Detection
Check all loop parameters such as Current, Voltage, Resistance, AC Voltage and Ground Fault errors
The Piecal 532 4-20 mA/Voltage Loop Calibrator with Loop Diagnostics is the best tool for calibration, test, and diagnosing process loops. The Piecal 532 brings all the features you would expect from a loop calibrator and timesaving ones. Make adjustments with the EZ-Dial knob or test limits with the Dual Action EZ-Check switch. Powerful ramping functions are only a button away on the Piecal 532. Save potentially hours of troubleshooting time on problem loops with the Piecal 532’s unique Loop Diagnostic Mode.
In Piecal's 532 Loop Diagnostic Mode, the loop current, voltage, impedance, AC voltage, and mode of operation are all displayed simultaneously eliminating the need of a DMM connection. Loop diagnostics is available in every mode of operation and truly is a diagnostic monitor, as parameters are continuously updated in real time. The smart diagnostic tool even indicates the most likely cause of loop failure! Loop Diagnostic features the ability to measure ground fault error caused by faulty wiring, flooded conduit and corrosion bridges.
제품사양
| Specifications | ||
| Function | Description | |
| Common Specifications for all current modes | ||
| Ranges | 00.000 to 24.000 mA | |
| Accuracy | ≤ ± (0.012 % of Reading + 0.004 mA) | |
| Temperature effect | ≤ ± 50 ppm/°C of Range | |
| Resolution(s) | 00.001 mA and 0.01% | |
| Source/Power and Measure 2-Wire Transmitter Specifications | ||
| Loop Compliance Voltage | ≥ 24 Volts | |
| Loop Drive Capability | 1200 Ω at 20 mA for entire battery life, 950Ω w/HART® mode enabled | |
| Miscellaneous | Open loop or out of compliance conditions are indicated by appropriate error display | |
| Battery life in: Source mode ≥ 18 hrs at 12mA typical (HART disabled) Power measure ≥ 10 hrs at 12mA typical | ||
| HART protocol mode is a selectable option at turn on. HART® protocol mode places a 250Ω resistor in series with the output | ||
| Selectable EZ-Step(s) for Source Mode/2-Wire Transmitter Simulation: 2 to 16 selectable step settings (Step size is determined by the selected high & low ranges) | ||
| Selectable time settings for stepping
and soak: STEP: 5 to 900 seconds SOAK: 0 to 900 seconds | ||
| 2-Wire Transmitter Simulation Specifications | ||
| Voltage Burden | ≤ 2 V at 20 mA | |
| Overload/Current Limit Protection | nominal ≤ 24 mA | |
| Loop Voltage Limits | 2-60 VDC | |
| Miscellaneous | Open loop or out of compliance conditions are indicated by appropriate error display | |
| Battery life ≥ 40 hour typical | ||
| Selectable EZ-Step(s) for Source Mode/2-Wire Transmitter Simulation | ||
| 2 to 16 selectable step
settings: Step size is determined by the selected high & low ranges | ||
| Selectable time settings for stepping
and soak: STEP: 5 to 900 seconds SOAK: 0 to 900 seconds | ||
| Read mA Specifications | ||
| Voltage burden | ≤ 2V at 20 mA | |
| Overload/Current limit protection | nominal ≤24 mA | |
| Battery life | Typical ≥ 40 Hours | |
| Voltage Specifications | ||
| Source Range | Range | 0.000 to 24.000 VDC |
| Output Resistance | ≤0.3 Ω | |
| Source Current | ≥20.000 mA with Flashing indicator for over range | |
| Accuracy | ≤±(0.012%RDG + 0.004 V) ±50ppm/°C of range | |
| Battery life | > 40 hour typical | |
| Read Range | Range | 0.000 to 24.000 VDC then 24.01 to 30.00
(with 4X over range) | Auto Ranging |
| Resolutions | 0.001 V up to 24 V, 0.01 V up to 30.00 V | |
| Temperature Effect | ≤ ± 100 ppm/°C of range | |
| Input Resistance | ≥ 1 MΩ | |
| Accuracy | 0.000 to 24.000 VDC ≤ ± (0.012%RDG + 0.004 V) 24.01 to 30.00 VDC ≤ ± (0.025 % of reading ±0.04 V) | |
| Voltage burden | ≤ 1V at 20 mA | |
| Overload/Current Limit Protection | 25 mA nominal | |
| Loop Voltage Limits | 2-42 VDC | |
| Miscellaneous | Error Display | Open loop or out of compliance conditions are indicated by flashing the bar graph |
| Battery life | ≥ 40 hour typical | |
| General Specifications:
(Unless otherwise indicated all specifications are rated from a nominal 23 °C, 70 % RH for 1 year from calibration) | ||
| Temperature Range | Operating | -20 to 60 °C (-5 to 140 °F) |
| Storage | -30 to 60 °C (-22 to 140 °F) | |
| Relative Humidity Range | 10 % ≤RH ≤90 % (0 to 35 °C), Non-condensing | |
| 10 % ≤RH≤ 70 % (35 to 60 °C), Non-condensing | ||
| Size | 7.00 X 3.30 X 2.21 inches (177.8 x 83.8 x 56.1mm) | |
| Weight | 12.0 oz (340 grams) | |
| Battery | 9V Alkaline | |
| Optional 120 VAC 50/60 Hz AC adaptor available | ||
| Miscellaneous | Low battery indication with nominal 1 hour of operation left | |
| Over-voltage protection to 120 Vrms (rated for 30 seconds) or 240 Vrms (rated for 15 seconds) | ||
| Bar graph display with 1% resolution of 4-20 mA signal scale | ||
| High contrast graphic liquid crystal display with 0.45" (11.4 mm) high digits | ||